>> PRODUCTS > Sensors > P3xx
|
 |
|
P3xx
is a hydrostatic level sensor, that works by measuring
the water pressure which is proportional to the
water level in a tank. The output is a standard
two-wire, 4-20 mA current loop, which corresponds
to the full scale of 0-100 mBar for P300, 0-200
mBar for P320, 0-300
mBar for P330, 0-400 mBar for P340 and 0-500 mBar
for P350.
The sensor needs an air isolated mounting method.
A so called Level Pipe streching vertically
along the tank should be adequate. The position
of the sensor should be above the highest water
level. |
| |
| Product
Specifications |
| |
Direct connection
to level pipe
| |
|
Pressure
input: |
| |
2 wire operation
| |
|
0-100 mbar
(for P300) |
| |
4-20 mA output
| |
|
0-200 mbar
(for P320) |
| |
Air isolated
input
| |
|
0-300 mbar
(for P330) |
| |
| |
|
0-400 mbar (for P340) |
| |
| |
|
0-500 mbar
(for P350) |
Technical Specifications
|
Excitation Voltage |
24 V (18-30 V) DC
|
|
Linearity |
< % 1
|
|
Input |
0-100, 200, 300, 400, 500 mbar
|
|
Temperature Range |
0 - 60 °C
|
| Media
Isolation |
Air
|
|
Mechanical Connection |
1/4" BSP
|
|
Output |
4-20 mA
|
|
Environmental Rating |
IP65
|
| Overpressure
|
750 mbar
|
|
Weight |
145 gr
|
|
Load Driving |
500 Ohm, 24 V DC
|
|
Case |
316SS
|
PDF Brochure
|
|